With the continuous development of technology, air conditioners have spread to every household. However, for some large shopping malls and medical centers, only the use of air conditioners is not enough. The emergence of ceiling-mounted air conditioners solves these problems. What are the installation methods for the ceiling-mounted air conditioning unit? What are the recommendations for a good ceiling-mounted air conditioning unit? The answers are all below.


吊顶式空调机组


First, the installation of ceiling type air conditioning unit


1. The ceiling type air conditioning unit should be installed horizontally in the ceiling sandwich. The side of the condensing water pipe is allowed to be five thousandths lower, but it is not allowed to be high to ensure the smooth discharge of condensed water. The unit should be fully installed in the maintenance space.


2. The condensate drain associated with the unit shall be provided with a water seal and the water seal shall be of sufficient height.


3. The water cooler of the air cooler is to be moved in and out, and a shut-off valve and a filter should be installed at the water inlet.


4. The air ducts linked by the fish unit need to be flexibly linked, and the water pipes linked with the unit should be wound around, and the torque should not be too large when taking over, so as to avoid loss of the heat exchanger. And the pipeline must be supported separately, and the heavy one is tolerated by the motor unit.


5. The power supply of the unit is 380V, 50Hz. The power supply meets the requirements before it can be connected to the motor. After the power is turned on, check whether the fan is turning correctly. If it is reversed, stop the power supply and change the phase sequence.


6. The fan motor should have good grounding, and there must be overload, overheating, missing items and other reliable protection.


Second, the product recommendation of ceiling type air conditioning unit


Cherry blossom central air conditioning 2P/3/5 horses cold and cold single ceiling machine ceiling machine embedded ceiling machine air conditioner, embedded ceiling air conditioner, four sides of the wind; ceiling installation, save space; three-dimensional uniform air supply, fast and warm and comfortable; silent operation Comfortable enjoyment; anti-fouling design; maintenance and cleaning; multiple controls; easy to use. 3 suitable for 30-40 square meters, 5 for 60-80 square. The anti-condensation design of the wind vane, using a unique groove process, ingeniously improved the shape of the wind vane, effectively preventing dew condensation. Powerful core, international leading technology compressor, fast and hot, high efficiency.


吊顶式空调机组


Third, ceiling type air conditioning unit operation and maintenance


1. The unit's hot and cold medium should be pure softened water, and its working pressure should not exceed 1.6Mpa.


2. The fan bearing temperature rise during normal operation of the unit should not exceed 40 °C.


3. The outlet pipe of the unit is equipped with an exhaust valve. Before the first operation and the hot and cold conversion, the air release valve must be opened to drain the air in the heat exchanger and the pipeline to avoid affecting the heat transfer effect. The total cold water temperature of the unit in summer is not lower than 5 °C, and the heating temperature in winter should not be higher than 80 °C.


4. When the new wind turbine in the cold region is open, the heater should be turned on for 5-10 minutes, then the blower should be started to prevent a large amount of cold air from forming ice plugs in the heat exchanger; when shutting down, the fresh air valve should be closed first. Turn off the heater, preferably turn off the blower.


5. When the unit is not used for a long time in winter, the coiled water should be drained and dried with compressed air. If the water cannot be blown clean, antifreeze should be added to the tube. If the unit does not operate temporarily during the winter period, it should ensure that there is hot water circulation in the tube to prevent rust and frost. In addition to winter, when the heat exchanger is deactivated in other seasons, the heat exchanger should also be filled with water to reduce erosion.


6. The filter should be cleaned regularly to ensure the use of the unit. If the air volume is reduced, it is generally caused by excessive dust accumulation in the filter.


7. After the unit is operated for one month, check whether the lifting bolts are loose.


Through the introduction of the above-mentioned small series for the ceiling-mounted air conditioning unit, I believe that everyone has a certain understanding, the above is the full content of the ceiling-mounted air conditioning unit, I hope this article is helpful to friends in need! For more information on decoration, please continue to pay attention to the decoration home network!